Document Citation: Wis. Adm. Code Comm 77.23

Header:
WISCONSIN ADMINISTRATIVE CODE
DEPARTMENT OF COMMERCE
CHAPTER COMM 77. THEATERS AND ASSEMBLY HALLS


Date:
08/31/2009

Document:
Wis. Adm. Code Comm 77.23 (2011)

Comm 77.23 Relief outlets

Every booth or room housing projection, sound or other equipment which constitutes a fire, smoke, explosion or fuming hazard shall be equipped with one or more gravity outlets extending upward from the ceiling through the roof. The net area of such gravity relief outlets shall be equal to one percent of the room or booth floor area, but not less than 12 inches in diameter. Such outlets shall be constructed as sheet metal ducts having double walls with 1/2 inch air spaces between, or better construction. Where a relief outlet passes through, or is within 18 inches of any combustible construction, or passes through any other occupancy, approved masonry flues as specified for chimneys, shall be used. The relief outlets shall be equipped, at the booth or room outlets, with a gravity shutter which will open automatically under excessive heat conditions. The automatic shutter shall normally be tightly closed where mechanical exhaust ventilation is required in the same room.